Hi, We are going to install a Kerosene Hydrotreater Unit. Is it required to fit connection strips in the Aviation Turbine Fuel lines flanges starting from downstream of reactor?
Answers
29/03/2020
|
A:
|
J Rout, B. Tech, routjhr@gmail.com
All the flanges in the liquid hydrocarbon service like ATF should be suitably fitted with connection strips to ensure continuity along the pipelines.
|
22/02/2020
|
A:
|
keith bowers, B and B Consulting, kebowers47@gmail.com
No. Any tankage with any vapor space must be appropriately grounded to dissipate any static electricity as the vapor space will likely be above LEL. Many refiners inject anti-static agent PRIST(only FAA Approved)into rundown lines of turbine fuel to prevent static charge accumulation.
|